7 - 2 7
7 UPS Operation
7.2.6 Battery Mode Turn-off Procedures (Parallel)
y
Press the
OFF
button
of one of the parallel UPSs for three to ten seconds and re-
lease it after you hear one beep. The LCD shows the message:
‘SHUTDOWN UPS?’
.
Select
‘YES’
and press the function key below the symbol ‘
’
WRFRQ¿UP\RXUVHOHF
-
tion.
1. If the remaining parallel UPSs’ total capacity exceeds the total critical loads, the
inverter of the UPS that you turned off will automatically shut down, and the critical
loads will be equally shared by the remaining parallel UPSs.
The status of the LCD and LEDs for the UPS that you turned off:
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD NOT POWERED
TO BROWSE EVENT
(004)
PRESS
Fault
The status of the LCD and LEDs for the remaining parallel UPSs:
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD PROTECTED
ON BATTERY
TO BROWSE EVENT
(004)
PRESS
Fault
1
Switch off the Output Switch (Q4) of the UPS that you turned off, and wait until the
UPS’s power module finishes discharging. During the discharging process, the
Inverter Start-up LED
LOOXPLQDWHV$IWHUWKHSRZHUPRGXOH¿QLVKHVGLVFKDUJLQJ
the Inverter Start-up LED
is off.
Содержание DPS-500K
Страница 38: ...3 12 Ultron DPS Series...
Страница 46: ...4 8 Ultron DPS Series...
Страница 80: ...6 12 Ultron DPS Series...
Страница 110: ...7 30 Ultron DPS Series...
Страница 132: ...8 22 Ultron DPS Series...
Страница 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Страница 135: ...10 1 10 Maintenance Maintenance 10...
Страница 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Страница 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 148: ...A1 4 Ultron DPS Series...
Страница 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 151: ......
Страница 152: ...5013238900...