7 - 9
7 UPS Operation
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
5
Press
the
ON
button
on the control panel for three to ten seconds and release
it after you hear one beep. The following screen appears.
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
SELF DIAGNOSIS
ON AUTO BYPASS
BYPA.
MAIN
6
During the start-up testing period, the system starts up the inverter, the Inverter
Start-up LED
lights up, and the system begins synchronization with the bypass
AC source.
7
After synchronization, the UPS will automatically switch from bypass mode into
inverter mode, and the inverter will supply power to the output. In the meantime,
the Bypass Power Supply LED
turns off, the Inverter Power Supply LED
illuminates, and the following screen appears.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD PROTECTED
ON LINE