8 - 1 2
Ultron DPS Series
y
BAT STRINGS
Set up how many battery strings are used.
y
BAT CUT OFF VOLT (V)
Set up battery low voltage. In battery mode, when the battery low voltage is reached,
the battery power will cut off, the UPS will shut down, and the connected loads won’t be
protected.
y
COMMON BAT
Set up whether batteries need to be shared in parallel mode.
y
TEST DURATION (MIN)
Set up how long the battery test should last.
y
TEST FAIL VOLT (V)
Set up test fail voltage. When the battery voltage is under the test fail voltage, it means
battery fail.
y
INSTALL DATE (Y-M-D)
Set up battery installation date.
y
NEXT REPLACE DATE (Y-M-D)
Set up battery replacement date.
8.7.4 Charger Setup
5RXWH0DLQ6FUHHQĺ0DLQ0HQXĺ8366HWXS &RQWUROĺ&KDUJHU6HWXS
In the
CHARGER SETUP
VFUHHQVKRZQEHORZ\RXFDQVHWXSÀRDWFKDUJHYROWDJHERRVW
charge voltage, and charge current.
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
CHARGER SETUP
FLOAT CHARGE VOLT(V)
BOOST CHARGE VOLT(V)
CHARGE CURRENT(A)
AUTO BOOST CHARGE
AUTO BOOST CHARGE PERIOD (MONTH)
AUTO BOOST CHARGE TIME (HOUR)
274
284
40
ON OFF
06
12
Содержание DPS-500K
Страница 38: ...3 12 Ultron DPS Series...
Страница 46: ...4 8 Ultron DPS Series...
Страница 80: ...6 12 Ultron DPS Series...
Страница 110: ...7 30 Ultron DPS Series...
Страница 132: ...8 22 Ultron DPS Series...
Страница 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Страница 135: ...10 1 10 Maintenance Maintenance 10...
Страница 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Страница 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 148: ...A1 4 Ultron DPS Series...
Страница 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 151: ......
Страница 152: ...5013238900...