7 - 2 8
Ultron DPS Series
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD NOT POWERED
TO BROWSE EVENT
(004)
PRESS
2
Switch off the UPS's connected external battery cabinets’ circuit breakers or fuses.
The Output Switch LED
shuts off and the following screen appears.
NOTE:
If you need to turn off the remaining parallel UPSs, please repeat the
procedures above.
2. If the total critical loads exceed the remaining parallel UPSs’ total capacity, all
parallel UPSs’ inverters will shut down and inverter static switches will automatically
turn off. At this moment, no power supplies to the critical loads.
1
Wait until all parallel UPSs’ power modules finish discharging. During the
discharging process, each Inverter Start-up LED
illuminates. After the power
PRGXOHV¿QLVKGLVFKDUJLQJHDFK,QYHUWHU6WDUWXS/('
is off.
2
Turn off each unit’s Output Switch (Q4) and each unit’s connected external battery
cabinets’ circuit breakers or fuses.
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD NOT POWERED
TO BROWSE EVENT
(004)
PRESS
Содержание DPS-500K
Страница 38: ...3 12 Ultron DPS Series...
Страница 46: ...4 8 Ultron DPS Series...
Страница 80: ...6 12 Ultron DPS Series...
Страница 110: ...7 30 Ultron DPS Series...
Страница 132: ...8 22 Ultron DPS Series...
Страница 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Страница 135: ...10 1 10 Maintenance Maintenance 10...
Страница 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Страница 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 148: ...A1 4 Ultron DPS Series...
Страница 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 151: ......
Страница 152: ...5013238900...