5 - 1 5
5 Installation and Wiring
WARNING:
1. When UPSs are paralleled, the length of each unit’s input cables plus
output cables must be the same. This ensures that the parallel UPSs can
equally share the critical loads in bypass mode.
2. Only UPSs with the same capacity, voltage and frequency can be paralleled;
otherwise, parallel functions will fail.
(Figure 5-14: Parallel Units Single Input Wiring Diagram)
UPS 1
UPS 2
UPS 8
I/P
LOAD
Main Input
Main Input
Main Input
Output
Output
Output
Parallel Port
Parallel Port
Parallel Port
Parallel Port
Pa
rallel C
able
3Ø4W
3Ø4W
Pa
rallel C
able
y
Dual Input (Parallel Units)
When there are two AC power sources, parallel units’ wiring procedures are as follows.
1
Follow
6LQJOH,QSXW'XDO,QSXW0RGL¿FDWLRQ
to modify the parallel UPSs
into dual input.
2
Follow the procedures
1
~
6
stated in the section of
Single Input (Single
Unit)
.