7 - 3
7 UPS Operation
2
Switch on the Bypass Switch (Q2). After initialization, all fans start running, the Bypass
AC Source LED
and the Bypass Power Supply LED
illuminate, and the
following screen appears.
2010 - 06 - 01
11 : 59 : 59
BYPA.
MAIN
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
TO BROWSE EVENT
(004)
PRESS
3
Turn on the UPS Output Switch (Q4), the Output Switch LED
illuminates and the
fol-lowing screen appears. Now the bypass supplies power to the output.
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
LOAD UNPROTECTED
ON AUTO BYPASS
TO BROWSE EVENT
(004)
PRESS
BYPA.
MAIN
4
Turn on the Input Switch (Q1), the Main AC Source LED
illuminates, and the UPS’s
DC BUS voltage starts establishing.
5
Press
the
ON
button
on the control panel for three to ten seconds and release it
after you hear one beep. The following screen appears.
BYPA.
MAIN
BYPA.
MAIN
2010 - 06 - 01
11 : 59 : 59
U N I T : # 1 . 1
SELF DIAGNOSIS
ON AUTO BYPASS
Содержание DPS-500K
Страница 38: ...3 12 Ultron DPS Series...
Страница 46: ...4 8 Ultron DPS Series...
Страница 80: ...6 12 Ultron DPS Series...
Страница 110: ...7 30 Ultron DPS Series...
Страница 132: ...8 22 Ultron DPS Series...
Страница 133: ...9 1 9 Optional Accessories 9 Optional Accessories...
Страница 135: ...10 1 10 Maintenance Maintenance 10...
Страница 137: ...11 1 11 Troubleshooting 11 Troubleshooting...
Страница 145: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1...
Страница 148: ...A1 4 Ultron DPS Series...
Страница 149: ...A2 1 Appendix 2 Warranty Warranty A2...
Страница 151: ......
Страница 152: ...5013238900...