D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 1 4
_5
97
40152
Pickup setpoint
(active power demand
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
98
40153
99
40154
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
9A
40155
Dropout setpoint
(active power demand
value below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
9B
40156
9C
40157
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Reactive Power Demand
9D
40158
Alarm enable
0: Disable
1: Enable
word
2
R/W
9E
40159
Pickup setpoint
(reactive power
demand value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
9F
40160
A0
40161
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
A1
40162
Dropout setpoint
(reactive power
demand value below
this value clears
alarm)
0.000 – 99999.999
float
kW
4
R/W
A2
40163
A3
40164
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...