D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 1 0
_5
61
40098
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
62
40099
Dropout setpoint (total
active power value
below this value
clears alarm)
0.000 – 99999.999
float
kW
4
R/W
63
40100
64
40101
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Over Reactive Power
65
40102
Alarm enable
0: Disable
1: Enable
word
2
R/W
66
40103
Pickup setpoint (total
reactive power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kVAR
4
R/W
67
40104
68
40105
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
69
40106
Dropout setpoint (total
reactive power value
below this value
clears alarm)
0.000 – 99999.999
float
kVAR
4
R/W
6A
40107
6B
40108
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Apparent Power
6C
40109
Alarm enable
0: Disable
1: Enable
word
2
R/W
6D
40110
Pickup setpoint (total
apparent power value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kVA
4
R/W
6E
40111
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 126: ...DPM C530 Operation Manual A 6 _A _1 MEMO...