D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 1 8
_5
D1
40210
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
D2
40211
Dropout setpoint (DUI
value below this
value, alarm cleared)
0.000 – 99999.999
float kW / m
2
4
R/W
D3
40212
D4
40213
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over EUI
D5
40214
Alarm enable
0: Disable
1: Enable
word
2
R/W
D6
40215
Pickup setpoint (EUI
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
kWh/
m
2
4
R/W
D7
40216
D8
40217
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
D9
40218
Dropout setpoint (EUI
value below this
value, alarm cleared)
0.000 – 99999.999
float
kWh/
m
2
4
R/W
DA
40219
DB
40220
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Meter Reset
DC
40221
Alarm enable
0: Disable
1: Enable
word
2
R/W
Alarm – Phase Rotation
DD
40222
Alarm enable
0: Disable
1: Enable
word
2
R/W
DE
41291
BACnet Device ID
(H)
0 – 63
word
2
R/W
DF
41292
BACnet Device ID (L) 0 – 65535
word
2
R/W
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 126: ...DPM C530 Operation Manual A 6 _A _1 MEMO...