D P M – C 5 3 0 O p e r a t i o n M a n u a l
5 - 8
_5
45
40070
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
46
40071
Dropout setpoint
(phase voltage value
below this value
clears alarm)
0.000 – 99999.999
float
V
4
R/W
47
40072
48
40073
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Under Voltage L–N
49
40074
Alarm enable
0: Disable
1: Enable
word
2
R/W
4A
40075
Pickup setpoint
(phase value below
this value triggers
alarm)
0.000 – 99999.999
float
V
4
R/W
4B
40076
4C
40077
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
4D
40078
Dropout setpoint
(phase voltage value
exceeding this value
clears alarm)
0.000 – 99999.999
float
V
4
R/W
4E
40079
4F
40080
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Voltage Unbalance
50
40081
Alarm enable
0: Disable
1: Enable
word
2
R/W
51
40082
Pickup setpoint (over
voltage unbalance
value exceeding this
value triggers alarm)
0.00 – 99.99
float
%
4
R/W
52
40083
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 126: ...DPM C530 Operation Manual A 6 _A _1 MEMO...