B0
40177
(frequency value
below this value
clears alarm)
R/W
B1
40178
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Under Frequency
B2
40179
Alarm enable
0: Disable
1: Enable
word
2
R/W
B3
40180
Pickup setpoint
(frequency value
below this value
triggers alarm)
0.0000 – 99.9999
float
Hz
4
R/W
B4
40181
B5
40182
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
B6
40183
Dropout setpoint
(frequency value
exceeding this value,
alarm cleared)
0.0000 – 99.9999
float
Hz
4
R/W
B7
40184
B8
40185
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over THD Voltage
B9
40186
Alarm enable
0: Disable
1: Enable
word
2
R/W
BA
40187
Pickup setpoint (THD
voltage value
exceeding this value
triggers alarm)
0.000 – 999.999
float
%
4
R/W
BB
40188
BC
40189
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 126: ...DPM C530 Operation Manual A 6 _A _1 MEMO...