D P M - C 5 3 0 O p e r a t i o n M a n u a l
4 - 4
_4
Set up Steps
1. Press MENU to display the setting menu.
2. Select 0 and press ENTER to enter the Setup menu.
3. Select 3 and press ENTER to enter the Communication menu.
4. Select Address and then press ENTER to set communication parameters.
5. After you select an option, use UP and DOWN to select the number for the address.
6. Press ENTER to confirm the setting and move to the next setting.
7. Repeat steps 5–6 until you complete the settings. Press ENTER to save the setting or press MENU to
cancel without saving the changes.
8. Select Protocol and then press ENTER to set the protocol parameters.
9. After you select an option, use UP and DOWN to select the mode (RTU or ASCII) for the address and
press ENTER to confirm the setting.
10. Repeat steps 5–6 until you complete the settings for the last digit. Press ENTER to save the setting or
press MENU to cancel without saving the changes.
11. Repeat the above steps for the Baud Rate, Data Bit, Parity, and Stop Bit settings.
12. Press MENU to go back to the setting menu.
4.2.4
Set up the Transformer Ratio
CT Primary:
Primary-side current transformer amperes; 1–9999 A, 1 A is default.
CT Secondary:
Secondary-side current transformer amperes; options are 1 A (default) and 5 A.
PT Primary:
Primary-side potential transformer voltage; 1–9999 V, 1 V is default.
PT Secondary:
Secondary-side potential transformer voltage; 1–9999 V, 1 V is default.
Set up Steps
1. Press MENU to display the setting menu.
2. Select 0 and press ENTER to enter the Setup menu.
3. Select 4 and press ENTER to enter the Transformer Ratio menu.
4. Select CT Primary and press ENTER to set the CT Primary settings.
5. After you select the option, use UP and DOWN to select the number for the ampere or voltage.
6. Press ENTER to confirm the setting and move to the next setting.
7. Repeat steps 5–6 until you complete setting the latest digit. Press ENTER to save the setting or
press MENU to cancel without saving the changes.
8. Repeat the above steps to set up the other settings.
9. Press MENU to go back to the setting menu.
Содержание DPM-C530
Страница 2: ......
Страница 3: ......
Страница 10: ...DPM C530 Operation Manual 1 4 _1 _1 MEMO...
Страница 16: ...DPM C530 Operation Manual 2 6 _2 2 4 Dimensions Front Unit mm Back Unit mm...
Страница 35: ...5 1 5 Chapter 5 Parameters and Functions Table of Contents 5 1 Overview of Parameters 5 2...
Страница 117: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 120: ...DPM C530 Operation Manual 6 4 _6 Memo...
Страница 121: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...