HD35
- 100 -
V1.12
12
MODBUS
In MODBUS communication the base unit works as a multiplexer (i.e., as an interface) to address
MODBUS commands from PC/PLC to wireless network devices. That means that the address of a
wireless device (for ex. a data logger) which is not physically connected to the RS485 (MOD-
BUS-RTU) or LAN (MODBUS TCP/IP) network can be added to the MODBUS command: the base
unit, physically connected to the RS485 or LAN network, will intercept the command and will send
it to the interested wireless device. The wireless device will execute the command and reply to the
base unit; this will send back the reply to the PC/PLC. In order for a wireless device to be ad-
dressed successfully, devices with the same MODBUS address as that of wireless devices should
not be present in RS485 or LAN network.
The device general information can be read through the function code 0x2B/0x0E. It consists
of:
•
Manufacturer (Delta OHM)
•
Model
•
Firmware version
The complete list of MODBUS registers is shown below. According to the device model, some of
the listed registers could not be present if not significant for that particular model (for ex., CO
2
measurement will not be available if it is not measured by the data logger). If you try to read a
register that is not present, the instrument returns the fixed value 32767. In case of doubt on
the registers actually available in a particular model, use the function " Download the list of
MODBUS registers of the device " included in the Settings sections of HD35AP-S software (see
software instructions).
The following conventions have been used in the tables:
o
AP = base unit, ED = data logger, RE = repeater, AL = alarm module
AP, ED, RE, AL columns indicate the device where the parameter is available.
o
Type: b = bit, B = 8 bits (Byte), W = 16 bits without sign (Word), SW = 16 bits with sign
o
(x10) = decimal value expressed as an integer (e.g., if the content of the register is 184,
the value is to be intended as 18,4).
o
(x100) = centesimal value expressed as an integer (e.g., if the content of the register is
500, the value is to be intended as 5,00).
The commands for requesting units of measurement return an index according to the corre-
spondence indicated in the table below:
TAB. 12.1: indexes of the units of measurement
Index Unit of
meas.
Index Unit of
meas.
Index Unit of
meas.
Index
Unit of
meas.
Index
Unit of
meas.
0
°C
12
mmH
2
O
24
Wh/m
2
36
m
2
/s
48
dB
1
°F
13
inchHg
25
kWh/m
2
37
g
(*)
49
dBA
2
%UR
14
inchH
2
O
26
J/m
2
38
mm
50
kWh
3
g/m
3
15
kgf/cm
2
27
µJ/cm
2
39
inch
51
l/s
4
g/kg
16
PSI
28
V
40
Counts
52
l/min
5
mbar
17
m/s
29
mV
41
mm/h
53
gallon/min
6
bar
18
km/h
30
mA
42
inch/h
54
m
3
/min
7
Pa
19
ft/s
31
ppm
43
counts /h
55
m
3
/h
8
hPa
20
mph
32
Hz
44
mW/m
2
56
µmol/(m
2
s)
9
kPa
21
knot
33
%
45
m
10
atm
22
W/m
2
34
degrees
46
s
11
mmHg
23
µW/cm
2
35
lux
47
µW/lumen
255
Not
defined
(*)
Gravity acceleration