HD35
- 103 -
V1.12
Address Type
Input Register description
AP ED RE AL
37
B
VWC probe output alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
46
SW T
EMPERATURE
with sensor integrated in RH module in the set
measurement unit (x10). Only for models …TVI and …AB.
47
B
Alarm for temperature with sensor integrated in RH module:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
Only for models …TVI and …AB.
48
SW
RELATIVE
H
UMIDITY
in % (x10). Only for models …TVI and …AB.
49
B
Relative humidity alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
Only for models…TVI and …AB.
50
SW T
EMPERATURE
with NTC10K sensor of channel 3 in the set
measurement unit (x10).
51
B
Alarm for temperature with NTC10K sensor of channel 3:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
52
SW W
IND SPEED
(cup anemometer) in the set measurement unit
(the multiplier depends on the set unit).
53
B
Wind speed (cup anemometer) alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
54
SW W
IND DIRECTION
(wind vane) in degrees.
55
B
Wind direction (wind vane) alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
56
SW D
IFFERENTIAL
P
RESSURE
for the range r3 in the set measurement
unit (the multiplier depends on the set unit).
57
B
Differential pressure alarm for the range r3:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
58
SW W
IND CHILL
in the set measurement unit (x10).
59
B
Wind chill alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
60
SW D
IFFERENTIAL
P
RESSURE
for ranges r1 and r2 in the set meas-
urement unit (the multiplier depends on the set unit).
61
B
Differential pressure alarm for ranges r1 and r2:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
62
SW D
IFFERENTIAL
P
RESSURE
for the range r4 in the set measurement
unit (the multiplier depends on the set unit).
63
B
Differential pressure alarm for the range r4:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
64
SW T
EMPERATURE
with Pt100 sensor of HP3517E… probe in the set
measurement unit (x10).
65
B
Alarm for temperature with Pt100 sensor of HP3517E… probe:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
66
SW P
YRANOMETER OUTPUT
in mV (x100).
67
B
Pyranometer output alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
68
SW UVA
IRRADIANCE
in mW/m
2
.
69
B
UVA irradiance alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
70
SW P
ROPORTION OF
UV
PRESENT
in µW/lumen.
71
B
Proportion of UV present alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
72
SW W
ET
B
ULB TEMPERATURE
measured by the natural ventilation wet
bulb probe, in the set measurement unit (x10).
73
B
Wet bulb temperature alarm:
0=OFF, 1=lower threshold alarm, 2=higher threshold alarm.
74
SW G
LOBE THERMOMETER TEMPERATURE
in the set measurement unit
(x10).