DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
37
17. Class 0x9F Custom Data Config
z
Instance0:
Attribute ID
Access rule
Name
Data type
1 Get
Revision
UINT
z
Instance1:
Attribute ID
Access rule
Name
Data Type
Default
1 Get/Set
resetparameter
USINT H’0066
2 Get/Set
dlen_in
USINT 2
words
3 Get/Set
dlen_out
USINT 2
words
9 Get/Set
Data_in
[0]
UINT H’2000
10 Get/Set
Data_in
[1]
UINT H’2001
11 Get/Set
Data_in
[2]
UINT H’FFFF
12 Get/Set
Data_in
[3]
UINT H’FFFF
17 Get/Set
Data_out
[0]
UINT H’2101
18 Get/Set
Data_out
[1]
UINT H’2102
19 Get/Set
Data_out
[2]
UINT H’FFFF
20 Get/Set
Data_out
[3]
UINT H’FFFF
z
Instance 2 EEPROM read/write
Attribute ID (decimal)
Access rule
Name
Data type
30
Get/Set
AMD reset parameter
H’0066
71
Get/Set
PLC reset parameter
H’0066
90
Get/Set
DTA reset parameter
H’0066
150
Get/Set
ASDA reset parameter
H’0066
Get/Set
DOP reset parameter
H’0066
200
Get/Set
Custom reset parameter
H’0066
z
Instance 3 Modbus baud rate setting
Attribute ID(decimal)
Access rule
Name
Range
Default
1
Get/Set
AMD baud rate setting
1 ~ 2
2
2
Get/Set
PLC baud rate setting
1 ~ 4
4
3
Get/Set
DT baud rate setting
1 ~ 2
2
4
Get/Set
ASDA baud rate setting
1 ~ 4
4
5
Get/Set
DOP baud rate setting
1 ~ 4
4
6 Get/Set
CUSTOM baud rate
setting
1 ~ 4
1
z
Common
Services
Implemented for
Service code
Class
Instance
Service name
005 Yes Yes
Reset
0x0E Yes Yes
Get_Attribute_Single
0x10 No Yes
Set_Attribute_Single
Содержание DeviceNet Slave Communication Module IFD9502
Страница 1: ...IFD9502 DeviceNet Slave Communication Module Application Manual...
Страница 2: ......