DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
40
3. When IFD9502 is connected to Delta DTA series temperature controller: By RS-485 communication.
IFD9502
DB9 female (RS-485)
DTA
RS-485 wiring terminal (RS-485)
DATA-
DATA+
(3)
(8)
5
9
4
8
3
7
2
6
1
DB9 female
DATA-
DATA+
DATA+
RS-485
DATA-
4. When IFD9502 is connected to Delta ASD-A series servo drive
z
By RS-232 communication
IFD9502
DB9 female (RS-232)
ASDA
CN3 connector (RS-232)
CN3 connector
1 3 5
2 4 6
5
9
4
8
3
7
2
6
1
DB9 female
TX
RX
RXD
TXD
(2)
(3)
GND (5)
(2)
(4)
(1)GND
z
By RS-485 communication
IFD9502
DB9 female (RS-485)
ASDA
CN3 connector (RS-485)
CN3 connector
5
9
4
8
3
7
2
6
1
DB9 female
DATA+
DATA-
(8)
(3)
1 3 5
2 4 6
(3) 485+
(5) 485+
(4) 485-
(6) 485-
5. When IFD9502 is connected to Delta DOP series human machine interface
z
By RS-232 communication
IFD9502
DB9 female (RS-232)
DOP
DB9 male (RS-232)
5
9
4
8
3
7
2
6
1
DOP COM1
5
9
4
8
3
7
2
6
1
DB9 female
TX
RX
RXD
TXD
(2)
(3)
GND (5)
(3)
(2)
(5)GND