DeviceNet Slave Communication Module IFD9502
DVP-PLC Application Manual
11
z
Common
Services
Implemented for
Service code
Class
Instance
Service name
0x32
No
Yes
Read PLC data
0x33
No
Yes
Write PLC data
3.
Format of inquiries and messages responded
z
IFD9502 allows you to inquire PLC by explicit messages. The format of inquiry is shown in the
table below.
Byte position
Data read from PLC
Data written into PLC
0
Frag [0]+XID+MAC ID
Frag [0]+XID+MAC ID
1
R/R [0]+Service code [0x32]
R/R [0]+Service code [0x33]
2
Class ID [0x96]
Class ID [0x96]
3
Instance ID
Instance ID
4
Position address LSB
Position Address LSB
5
Position address MSB
Position Address MSB
6
Number LSB
Service data LSB
7
Number MSB
Service data MSB
z
Explanation
“Position address” refers to the No. of the device in the register of PLC. For example, the
position address of M0 is 0 and that of D100 is 100.
“Number” refers to the number of PLCs. When the read device is a word device, “Number”
refers to the number of words read; when the read device is a bit device, “Number” refers to
the number of bits read.
Bit devices, S, X, Y and M in DVP-PLC allow the reading of maximum 16 bits and writing in
of only 1 bit (either 0 or 1). Devices T, C and D in DVP-PLC allow the reading of maximum 3
words and writing in of 1 word. See the table below.
Device in PLC
Max. length to be read allowed
Max. length to be written in allowed
S
16 bits
1 bit
X
16 bits
Not support
Y
16 bits
1 bit
M
16 bits
1 bit
T (bit device)
16 bits
1 bit
C (bit device)
16 bits
1 bit
T (word device)
3 words
1 word
C (word device)
3 words
1 word
D (word device)
3 words
1 word