Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-37
Group 3: Output Function Parameters
03 - 00
Multi-function Output terminal 1 (Relay)
Settings
00-21
Factory Setting: 01
Setting
Functions
Descriptions
00 Disabled
01 Indication
during
operation
The corresponding output will be closed during operation
(including DC braking time).
02 Master
frequency
attained
The corresponding output will be closed when output
frequency reaches master frequency command.
03
Zero Speed (including
shutdown)
The corresponding output will be closed when the AC drive
has no output voltage signal.
04
Over-torque
The corresponding output relay will be closed when the AC
drives output current exceeds the over-torque detection
level 06-04.
05
External Fault
The corresponding output will be closed when the EF is
enabled. (Pr. 04-00 to 04-03)
06
Low voltage detection
The corresponding output will be closed when the DC Bus
voltage drops below our threshold. The keypad will display
“Lu”.
07 Operation
Mode
indication
The corresponding output will be closed when the AC
drives “Operation Command” is controlled by the external
terminals.
08
Fault Indication
The corresponding output will be closed when AC drive
has experienced a fault.
09 Master
Frequency
Attained 1
The corresponding output will be closed when the AC
drives output frequency exceeds (Pr.03-08) Master
Frequency Attained 1.
10 Master
Frequency
Attained 2
The corresponding output will be closed when the AC
drives output frequency exceeds (Pr.03-09) Master
Frequency Attained 2.
11 Over
Temperature
indication
The corresponding output will be closed when the AC drive
temperature exceeds its rating.
12
Drive Ready
The corresponding output will be closed the when the AC
drive is ready and has no faults.
13
External Emergency Stop
(EF1)
The corresponding output will be closed when multi-
function input terminals (Pr.04-00 to 04-03) are set to
emergency stop and then activated.
14
Software braking output
The corresponding output will be closed when the AC
drives DC bus voltage exceeds (Pr.08-19) the braking
level.
15
OL or OL1 overload
warning
The corresponding output will be closed upon an overload
(OL or OL1) fault.
16
Low current indication
The corresponding output will be closed when the AC
drives output current is lower than the Low Current setting
(Pr.06-08).
Содержание AC Motor Drive VFD-G
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 17: ...Chapter 1 Introduction 1 8 Revision July 2008 EG03 SW V1 06 For 150 215HP Frame G Step 1 Step 2 Step 3 Step 4...
Страница 18: ...Chapter 1 Introduction Revision July 2008 EG03 SW V1 06 1 9 For 250 300HP Frame H Step 1 Step 2 Step 3 Step 4...
Страница 23: ...Chapter 1 Introduction 1 14 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 45: ...Chapter 2 Installation and Wiring 2 22 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 51: ...Chapter 3 Keypad and Start Up 3 6 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 141: ...Chapter 4 Parameters 4 90 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...