Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-87
When this parameter is set to 01: when positive control, the deviation equation is deviation =
detection signal - target value. When increasing output frequency will decrease detection value,
this setting should be chose.
10 - 03
Proportional Gain (P)
Unit: 0.1
Settings
0.0~10.0
Factory Setting: 1.0
This parameter is to set proportional gain (P). This gain determines the response degree of P
controller to feedback deviation. If gain value is large, the response is fast. But if the gain value
is too great, oscillation will occur. If gain value is small, the response is slow.
10 - 04
Integral Time (I)
Unit: 0.01
Settings
0.00~100.00 Sec
Factory Setting: 1.00
This parameter is set to integral gain of I controller. When much integral time is to be set, the
gain of I controller is small and the response is slow. The control ability to external is poor.
When less integral time is to be set, the gain of I controller is large and the response is fast.
The control ability to external is fast.
If the setting of integral time is too small, output frequency and system may occur oscillation.
If integral time is set to 0.00, I controller is closed.
10 - 05
Differential Time (D)
Unit: 0.01
Settings
0.00~1.00 Sec
Factory Setting: 0.00
This parameter is set to D controller gain. This gain determines D controller to the response of
change of deviation. Suitable differential time could decrease overshoot of P and I controller.
The oscillation will be attenuation and steady quickly. But if much differential time is to be set,
it may cause system oscillation.
Interference immunity ability is poor due to differential controller activates to change of
deviation. It’s not recommended to use, especially during interferences.
10 - 06
Upper Bound for Integral Control
Unit: 1
Settings
00~200%
Factory Setting: 100
This parameter could set the upper bound of I controller. In other words, upper bound for
integral control = (01-00) X (10-04) %
Содержание AC Motor Drive VFD-G
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 17: ...Chapter 1 Introduction 1 8 Revision July 2008 EG03 SW V1 06 For 150 215HP Frame G Step 1 Step 2 Step 3 Step 4...
Страница 18: ...Chapter 1 Introduction Revision July 2008 EG03 SW V1 06 1 9 For 250 300HP Frame H Step 1 Step 2 Step 3 Step 4...
Страница 23: ...Chapter 1 Introduction 1 14 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 45: ...Chapter 2 Installation and Wiring 2 22 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 51: ...Chapter 3 Keypad and Start Up 3 6 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 141: ...Chapter 4 Parameters 4 90 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...