Chapter 4 Parameters
|
Revision July 2008, EG03, SW V1.06
4-39
03 - 04
DC Fan Control
Factory Setting: 00
Settings
00: Fan runs on power up.
01: Fan begins upon a RUN command. Fan stops 1 minute after a STOP
command.
02: Fan begins upon a RUN command. Fan stops after a STOP command
03: Fan is controlled by temperature. Fan will be started at approximate
60°C.
This parameter determines DC fan control method.
03 - 05
Analog Output 1, (AFM1) 0~10Vdc
Factory Setting: 00
03 - 06
Analog Output 2, (AFM2) 0/4~ 20mA
Factory Setting: 01
Settings
00: Output frequency
01: Output current
02: Output voltage
03: Frequency command
04: Power factor loading
These
parameters
select
the content of the analog output signals AFM1 and AFM2.
Setting 00: 0-10V = 0 - (Pr.01-00)
Setting 01: 0-10V = 0 - (Double rated current)
Setting 02: 0-10V = 0 - (Pr.01-02)
Setting 03: 0-10V = 0 - Master Freq. command
Setting 04: 0-10V = 0.0 - output power factor 1.0
When using 0-20mA output, please refer to Pr. 3-14.
Maximum impedance loading of analog output 2 (AFM2) can’t be greater than 500 ohms.
03 - 07
Analog Output Gain 1
03 - 08
Analog Output Gain 2
Settings
01~200%
Factory Setting: 100
These parameters are to determine analog output gain.
The analog output is limited to 10V and 20mA. The gain is designed to offer a normally small
output signal to be enlarged for easier viewing on a meter.
Содержание AC Motor Drive VFD-G
Страница 1: ......
Страница 2: ......
Страница 3: ......
Страница 17: ...Chapter 1 Introduction 1 8 Revision July 2008 EG03 SW V1 06 For 150 215HP Frame G Step 1 Step 2 Step 3 Step 4...
Страница 18: ...Chapter 1 Introduction Revision July 2008 EG03 SW V1 06 1 9 For 250 300HP Frame H Step 1 Step 2 Step 3 Step 4...
Страница 23: ...Chapter 1 Introduction 1 14 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 45: ...Chapter 2 Installation and Wiring 2 22 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 51: ...Chapter 3 Keypad and Start Up 3 6 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...
Страница 141: ...Chapter 4 Parameters 4 90 Revision July 2008 EG03 SW V1 06 This page intentionally left blank...