Table 27. Operating temperature de-rating specifications
Operating temperature de-rating
Specifications
Up to 35°C (95°F)
Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above 950 m
(3,117 ft).
35°C to 40°C (95°F to 104°F)
Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above 950 m
(3,117 ft).
40°C to 45°C (104°F to 113°F)
Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above 950 m
(3,117 ft).
Standard operating temperature
Table 28. Standard operating temperature specifications
Standard operating temperature
Specifications
Continuous operation (for altitude less than 950 m or 3117
ft)
10°C to 35°C (50°F to 95°F) with no direct sunlight on the equipment.
Expanded operating temperature
Table 29. Expanded operating temperature specifications
Expanded operating temperature
Specifications
Continuous operation
5°C to 40°C at 5% to 85% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate continuously in temperatures as low
as 5°C and as high as 40°C.
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
≤ 1% of annual operating hours
–5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE:
Outside the standard operating temperature (10°C to
35°C), the system can operate down to –5°C or up to 45°C for a
maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum allowable
temperature by 1°C per 125 m above 950 m (1°F per 228 ft).
NOTE:
When operating in the expanded temperature range, system performance may be impacted.
NOTE:
When operating in the expanded temperature range, ambient temperature warnings may be reported in the System Event
Log.
Expanded operating temperature restrictions
•
Do not perform a cold startup below 5°C.
34
Technical specifications
Содержание PowerEdge R7425
Страница 9: ...Figure 1 Supported configuration PowerEdge R7425 system overview 9 ...
Страница 44: ...Option Description ...