DLS 300 / 450 / 600
49
Code 240.010.0001
•
“LITHIUM ” Menu
By accessing the “LITHIUM” menu, the Lithium battery type, make and model can be selected amongst
those supported by the DLS system.
By selecting a Lithium battery, the DLS system can be configured to interact only with the selected battery
type, make and model.
The Lithium battery configuration settings can be used only by qualified staff. Changing the settings by
unqualified staff could affect the correct operation of the system and relieves the manufacturer from all li
-
abilities, as well as invalidate the warranty.
Some additional settings can be accessed only in the INSTALLER mode, which requires a password to be
entered (see the section “LOGIN Menu”).
Parameters at installer level can only be accessed by qualified staff. Changing the installer level param
-
eters by unqualified staff could affect the correct operation of the system and relieves the manufacturer from
all liabilities, and invalidates the warranty.
6.6.5 “HOME AUTOMATION” Menu
Access the “HOME AUTOMATION” menu to set up the HOME AUTOMATION PCB (optional).
The references related to the independent programmable contacts on the HOME AUTOMATION PCB are:
LD1
→ Enable/disable LD1 relay
LD2
→ Enable/disable LD1 relay
LD3
→ Enable/disable LD1 relay
LD4
→ Enable/disable LD1 relay
GEN
→ Enable/disable GEN relay
AUX
→ Enable/disable AUX relay
The
LD1 ÷ LD4
and therefore the loads applied to the associated contacts are enabled by configuring the
following parameters, specific for each load:
•
LD ON/OFF
→ Select ON to enable the contact control. Select OFF to disable the contact control.
• P START
→ Select the threshold for the power coming from the PV generator, above which the contact
is enabled. The contact is enabled when the available power from the PV array is higher than the set
threshold. The contact is disabled when the available power from the PV array is lower than the set
threshold.
• START LD DAY
→ Select the days of the week when the contact is enabled to operate.
• START LD H
→ Select the time starting from which the contact is enabled to operate.
• STOP LD H
→ Select the time starting from which the contact is disabled to operate.
The GEN contact is activated to remotely control the auxiliary power generator and occurs according to the
following modes:
• GEN
→
The contact is activated when the system detects that at the same time the grid power is
unavailable and the battery is flat. The contact is disabled when one of the two statuses is restored.
With contact GEN enabled, the energy produced by the PV generator is used by the system to restore
the battery charge status.
The AUX contact is dedicated to remotely signal or monitor the external devices when an alarm condition
is detected by the system and is carried as shown below:
• AUX
→ The contact is enabled when the system detects a general alarm condition. The contact is
disabled when the alarm condition is removed.
Содержание DLS 300
Страница 4: ...4 Code 240 010 0001 DLS 300 450 600 Fig 01 ...
Страница 8: ...8 Code 240 010 0001 DLS 300 450 600 6 x Fig 05 ...
Страница 10: ...10 Code 240 010 0001 DLS 300 450 600 PV1 PV2 Fig 07 ...
Страница 11: ...DLS 300 450 600 11 Code 240 010 0001 PV Fig 08 ...
Страница 13: ...DLS 300 450 600 13 Code 240 010 0001 GEN N L PE PE N L PE GEN ON OFF REMOTE CONTROL OPTIONAL G Fig 10 ...
Страница 63: ...DLS 300 450 600 63 Code 240 010 0001 ...