DLS 300 / 450 / 600
55
Code 240.010.0001
9 TROBLESHOOTING
ALARM
TYPE
SOLUTION
E001
Converter monitoring sys-
tem fault.
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E002
Converter monitoring sys-
tem fault.
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E003
Incorrectly configured sys
-
tem.
•
Contact our technical support service.
E004
AC overcurrent.
•
Check the sizes and the system output connections.
•
Refer to the section “Connection”.
•
Should the problem persist, contact our technical support service.
E005
Faulty interface device
built in the system.
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E006
Faulty interlock device
built in the system.
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E007
Temperature inside the
system too high
•
Check the correct position of the inverter and that the installation
complies with the instructions provided in the sections "Positioning"
and "Mounting" of this manual.
•
Check that the ambient temperature is within the accepted range.
•
Check the correct operation of the cooling fans.
•
Check that there is no build up of dust near the air intakes.
•
Should the problem persist, contact our technical support service.
E008
Internal current leakage
•
Switch off and restart the system.
•
Refer to the sections “Switching off the system” and “Switching on
the system”
•
Should the problem persist, contact our technical support service.
E009
NEUTRAL line incorrectly
connected
•
Check that the input and output AC lines have the correct polarity.
•
Should the problem persist, contact our technical support service.
E010
Self-test failed (only rel-
evant in Italy CEI 0-21)
•
Make sure that the electrical connections are in good conditions.
•
Make sure that the mains voltage and frequency are within the range
required by standard CEI 0-21.
•
Should the problem persist, contact our technical support service.
E011
Mains voltage too high
•
Make sure that the mains voltage is within the range required by
local legislation.
•
Check the mains impedance.
•
If the voltage is outside the allowed range because of the conditions
of the local grid, contact the electricity provider to find out whether
the voltages at the connection point can be adjusted or ask for their
approval to change the operating limits.
•
If the voltage is within the allowed range, but the alarm persists,
contact our technical support service.
Содержание DLS 300
Страница 4: ...4 Code 240 010 0001 DLS 300 450 600 Fig 01 ...
Страница 8: ...8 Code 240 010 0001 DLS 300 450 600 6 x Fig 05 ...
Страница 10: ...10 Code 240 010 0001 DLS 300 450 600 PV1 PV2 Fig 07 ...
Страница 11: ...DLS 300 450 600 11 Code 240 010 0001 PV Fig 08 ...
Страница 13: ...DLS 300 450 600 13 Code 240 010 0001 GEN N L PE PE N L PE GEN ON OFF REMOTE CONTROL OPTIONAL G Fig 10 ...
Страница 63: ...DLS 300 450 600 63 Code 240 010 0001 ...