The value is programmed in AD-points: a converted digital value of the position feedback
voltage of the potentiometer.
Parameter 73
Angle prestop negative
Range
: 0 - 99
Unit
: AD value
Default
: 0
Function
This parameter has the same definition as parameter "Angle Prestop Positive" but only in the
negative direction of the angle adjustment (smaller angle).
Parameter 74
Angle reference table
Range
: -
Unit
: -
Default
: -
Function
Press ENTER to open the screen with the angle reference table. In this table, the relation
between the blade angle and the feedback voltage can be programmed.
Angle: program a known angle value for the blade.
AD-value: program the required feedback voltage for this angle. The feedback voltage must
be programmed in the range 0-4095, which represents the input voltage in the range 0-10V.
Use the diagnostic mode to find the correct AD-values. Move the blade to and angle, measure
the angle position and notice the corresponding AD-value from the analog input.
Parameter 75
Angle material table
Range
: -