6.7.2.
List of the parameters
Parameters Description
Adjustment range Factory
setting
P 01
DHW setpoint in
Auto
mode
25 to 70 °C
55 °C
P 02
DHW set point in
Eco
mode
25 to 65 °C
55 °C
P 04
Choice of mode for the DHW Comfort period:
4
0 = Use the time programs.
4
1 = Use the electricity tariff information input. Tells you whether or not
domestic hot water production is permitted (HP1 = not permitted => Contact
closed, HC0 = permitted => Contact open).
4
2 = Use the electricity tariff information input. Tells you whether or not
domestic hot water production is permitted (HP1 = not permitted => Contact
open, HC0 = permitted => Contact closed).
4
3 = Use the time programs. The status of the electricity tariff information
input is used to activate the Boost function with compressor only (HP1 =
Boost deactivated => Contact closed, HC0 = Boost activated => Contact
open).
4
4 = The status of the electricity tariff information input is used to activate
the Boost function with compressor only (HP1 = Boost activated => Contact
open, HC0 = Boost deactivated => Contact closed).
4
5 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost deactivated
=> Contact closed, HC0 = Boost activated => Contact open).
4
6 = The status of the electricity tariff information input is used to activate
the Boost function with compressor and back-up (HP1 = Boost activated
=> Contact open, HC0 = Boost deactivated => Contact closed).
0 - 6
0
P 06
Automatic switch to summer time (last Sunday in March) and winter time (last
Sunday in October):
4
0 = Function not active (for countries where the time change is done on
other dates or is not in use)
4
1 = Function activated
0 - 1
1
P 07
DHW setpoint in
Boost
mode
40 to 70 °C
62 °C
P 17
Protection by impressed current anode
4
0 = Deactivation
4
1 = Activation
0 - 1
1
P 18
Water volume contained in the DHW tank (x 10 l)
6 - 255
27
P 19
Water volume for one bath (l)
10 - 255
120
P 20
Maximum duration of the Boost mode (h)
1 - 10
6
P 22
Back-up type
4
0 = None
4
1 = Electrical back-up
4
2 = Hydraulic additional heating
0 - 2
1
P 23
Time delay for starting the electrical or hydraulic back-up in Automatic mode
(Hours)
0 - 10
5
P 24
Compressor start-up time (seconds)
60 - 255
120
P 26
Antilegionella function. The tank is overheated every Saturday from 1 o’clock to
6 o’clock (65 °C).
4
0 = Off
4
1 = Activated outside holiday periods
4
2 = Always activated
0 - 1
0
P 27
Compressor cut-off hysteresis in relation to the set point for the bottom domestic
hot water temperature sensor (only in Auto or Boost mode)
5 - 15
10
TWH 200E TWH 300E TWH 300EH
6. Commissioning