Parameters Description
Adjustment range Factory
setting
P 28
Maximum DHW temperature (bottom sensor) for compressor cut-off (°C) (only
in Auto or Boost mode)
35 - 50
45
P 29
Minimum duration of compressor operation (minutes)
3 - 10
3
P 30
Anti-short-cycle period between 2 compressor start-ups (minutes)
5 - 10
5
P 31
Hydraulic additional heating
4
0 = contact
R6
closed if there is an additional hydraulic heating request
4
1 = contact
R6
opened if there is an additional hydraulic heating request
0 - 1
0
P 32
DHW setpoint used for the antilegionella function
55 to 70 °C
65 °C
P 52
Difference in temperature between the tank temperature and the set point
before restarting the compressor
1 to 15 °C
3 °C
P 57
Minimum room temperature for compressor operation
–5 to 20 °C
–5 °C
P 58
Maximum room temperature for compressor operation
20 to 35 °C
35 °C
6.7.3.
Control system sequence
Control system sequence
Status Sub-status Operation
0
0
Appliance off
7
Compressor post-operation
1
1
Anti-short cycle activated
2
Wait for the start-up condition for domestic hot water production
3
Start-up of the fan and the defrosting valve
2
5
Compressor starts
6
Defrosting
3
1
Anti-short cycle activated
4
Additional heating starts
7
Compressor post-operation
4
5
Compressor starts
6
Defrosting
9
--
Blockage state
6.7.4.
Return to the factory settings
1. Press the
(
and
)
keys
simultaneously
for 5 seconds. The
rSt
menu is displayed.
C003495-C
3
1
4
3
4
1
2
MENU
MODE
6. Commissioning
TWH 200E TWH 300E TWH 300EH
54
19/01/2015 - 300026515-001-05