Installer level - Menu #NETWORK
(1)
Parameter
Adjustment range Description
Factory setting Customer setting
CASCADE:
ON
/
NO
ON
: System in cascade
NO
VM NETWORK
(2)
Specific menu: Enlist VMs in cascade
mode (See following chapter:
"Connect VMs only in cascade")
MASTER CONTROLLER
(3)
ON
/
NO
Configure this control system as
master on the bus
ON
SYSTEM NETWORK
(4)
Specific menu: Enlist generators or
VMs in cascade mode (See following
chapter: "Connecting appliances in
cascade")
FUNCT
(4)
CLASSIC
Operation in cascade: Successive
tripping of the various generators in
the cascade according to needs
CLASSIC
PARALLEL
Functioning in parallel cascade: If the
outside temperature is lower than the
PARALLEL CASC.
value, all
generators are started up at the same
time
PARALLEL CASC.
(5)
-10 to 20 °C
Outside temperature triggering all
stages in parallel mode
10 °C
TIMER GENE P. CASC
(3)
0 to 30 min
Minimum duration of post-operation of
the generator pump
0 mn
INTER STAGE TIMER
(3)
1 to 30 min
Time delay for starting up or shutting
down generators.
4 mn
SLAVE NUMBER
(6)
2 to 10
Set the network address of the
secondary generator
2
(1) The menu is displayed only if the
INSTALLATION
parameter is set to
EXTENDED
(2) The parameter is only displayed if
CASCADE:
is set to
NO
(3) The parameter is only displayed if
CASCADE:
is set to
ON
(4) The parameter is only displayed if
MASTER CONTROLLER
is set to
ON
(5) The parameter is only displayed if
FUNCT
is set to
PARALLEL
(6) The parameter is only displayed if
MASTER CONTROLLER
is set to
OFF
User level - Menu #SETTING
Parameter Adjustment range Description
Factory setting Customer setting
PERMUT
(1)
AUTO
/ 1 ... 10
This parameter is used to set the master boiler.
4
AUTO
: The master boiler switches automatically
every 7 days
4
1 ... 10: The master boiler is always the one
defined by this value
AUTO
(1) The parameter is only displayed if
CASCADE:
is on
ON
and
MASTER CONTROLLER
on
ON
n
Connecting appliances in cascade
It is possible, in a cascade configuration, to enlist generators and/or
VM iSystem as slaves. Proceed as follows:
1. Set parameter
CASCADE:
to
ON
.
5. Commissioning
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
92
20/01/2012 - 300026081-001-B