User level - Menu #SETTING
Parameter
Adjustment range Description
Factory setting
Customer
setting
CALIBR. ROOM C
(4)(1)(2)
Calibration of the room sensor on
circuit C
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
Room temperature
of circuit C
OFFSET ROOM C
(4)
(1)(3)
-5.0 to +5.0 °C
Room offset on circuit C: Is used to set a
room offset
Make this setting 2 hours after switching
on, when the room temperature has
stabilised
0.0
ANTIFR. ROOM C
(4)
0.5 to 20 °C
Room temperature antifreeze activation
on circuit C
6 °C
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter is only displayed if a room sensor is connected to the circuit concerned
(3) The parameter is only displayed if no room sensor is connected to the circuit concerned or the sensor has no influence
(4) The parameter is only displayed if the circuit concerned is actually connected
5.7.3.
Professional settings
1. Access the installer level: Press key
-
for around 5 seconds.
2. To set the following parameters:
4
Turn the rotary button to scroll through the menus or
modify a value.
4
Press the rotary button to access the menu selected
or confirm a value modification.
¼
For a detailed explanation of menu browsing, refer
to the chapter: "Browsing in the menus", page 66.
Installer level - Menu (#PRIMARY LIMITS)
Parameter
Adjustment range Description
Factory setting Customer setting
BOILER MAX
20 to 90 °C
Maximum boiler temperature
80 °C
MAX.R.HEAT(%)
(1)
0-100%
Maximum boiler output during heating
100%
MAX.DHW(%)
(1)(2)
0-100%
Maximum boiler output in DHW
100%
MIN.VENT.
(1)
1000-5000 rpm
Minimum fan speed
See table below
MAX.VENT.BOIL
(1)
1000-7000 rpm
Maximum fan speed setting in heating
See table below
MAX.VENT.DHW
(1)
1000-7000 rpm
Maximum fan speed setting in domestic
hot water
See table below
START RPM
(1)
1000-5000 rpm
Optimum start-up speed setting
See table below
MIN.PUMP SPEED
(1)
20-100%
Minimum pump speed
20 %
MAX.PUMP SPEED
(1)
20-100%
Maximum pump speed
60 %
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter is only displayed if
P.DHW:
is set to
PUMP
The parameter is only displayed if
P.DHW
is set to
PUMP
1
1
2
2
r
c
STD
(
'
t
v
0
2
4
6
8
10
12
14
16
18
22
24
20
p
b
AUTO
x c
r
j
M
g
m
SUNDAY 11:45
5"
TEMP.: 68°
C002235-F-04
5. Commissioning
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
84
20/01/2012 - 300026081-001-B