Installer level - Menu #PRIMARY INSTAL.P
(1)
Parameter
Adjustment range Description
Factory setting Customer
setting
BURN.MIN.RUN
0 to 180 seconds
Setting the burner minimum operation time (In
heating mode)
30 seconds
TIMER GENE P.
(1)
1 to 30 minutes
Maximum post-operation duration of the generator
pump
4 minutes
IN.BL
(1)
STOP HEAT
Configuration of the PCU BL inlet
If the contact is open, the heating is off. If the
parameter
P.DHW:
is set to
RV
, DHW production
nevertheless remains functional. Automatic restart
when the contact closes.
TOTAL STOP
TOTAL STOP
Configuration of the PCU BL inlet
If the contact is open, heating and DHW
production are off. Automatic restart when the
contact closes.
SAFETY MODE
Configuration of the PCU BL inlet
If the contact is open, the boiler goes into safety
lockout. The boiler needs to be reset to restart.
(1) The menu is displayed only if the
INSTALLATION
parameter is set to
EXTENDED
Installer level - Menu #SECONDARY INSTAL.P
Parameter
Adjustment range
Description
Factory
setting
Customer
setting
BUILD. INERTIA
(1)
0 (10 hours) to 10
(50 hours)
Characterisation of building's inertia:
0 for a building with low thermal inertia.
3 for a building with normal thermal inertia.
10 for a building with high thermal inertia.
Modification of the factory setting is
only useful in exceptional cases.
3 (22 hours)
CIRC.CURVE A
(2)
0 to 4
Heating curve of the circuit A
¼
1.5
ROOM INFL. A
(1)
0 to 10
Influence of room sensor A
¼
3
CIRC.CURVE B
(2)
0 to 4
Heating curve of the circuit B
¼
0.7
ROOM INFL. B
(1)
0 to 10
Influence of room sensor B
¼
3
CIRC.CURVE C
(2)
0 to 4
Heating curve of the circuit C
¼
0.7
ROOM INFL. C
(1)
0 to 10
Influence of room sensor C
¼
3
SCREED DRYING
NO, B, C, B+C
Drying the floor
¼
NO
START DRYING
TEMP
(3)
20 to 50 °C
Screed drying start temperature
20 °C
STOP DRYING
TEMP
(3)
20 to 50 °C
Screed drying stop temperature
20 °C
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) The parameter can be set to the heating curve by pressing key
f
(3) The parameter is only displayed if
SCREED DRYING
is other than
OFF
(4) The parameter is only displayed if
IN 0-10V
is set to
ON
.
(5) If a reversal valve is connected, DHW priority will always be total regardless of the setting.
5. Commissioning
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
86
20/01/2012 - 300026081-001-B