Controlling the pool circuit
The control system can be used to manage a swimming pool circuit
in both cases:
Case 1: The control system regulates the primary circuit (boiler/
exchanger) and the secondary circuit (exchanger/pool).
4
Connect the primary circuit pump (boiler/exchanger) to the
M
B
outlet on the connection terminal block. The temperature
MAX.CIRC.B
is then guaranteed during comfort periods on
programme
B
in summer and winter alike.
4
Connect the swimming pool sensor (package AD212) to the
S
DEP B
inlet on the connection terminal block.
4
Set the set point of the pool sensor using key
C
in the range 5 -
39°C.
Case 2: The pool has already a regulation system that is to be
kept. The control system only regulates the primary circuit
(boiler/exchanger).
4
Connect the primary circuit pump (boiler/exchanger) to the
M
B
outlet on the connection terminal block.
The temperature
MAX.CIRC.B
is then guaranteed during comfort
periods on programme
B
in summer and winter alike.
The swimming pool can also be connected to circuit
C
by
adding the AD249 option:
4
Make the connection to the terminal blocks marked
C
.
4
Set the parameters for circuit
C
.
n
Hourly programming of the secondary circuit pump
The secondary pump operates during programme
B
comfort periods
in summer and winter alike.
n
Stopping
To prepare your pool for winter, consult your pool specialist.
4.9.10.
Connecting a mixed tank
In winter mode, the boiler heats the DHW tank.
In summer mode, the tank is heated by the electrical
resistor.
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
4. Installation
20/01/2012 - 300026081-001-B
53