4.9.2.
Recommendations
WARNING
4
Only qualified professionnals may carry out electrical
connections, always with the power off.
4
The boiler is entirely pre-wired. Do not modify the
connections inside the control panel.
4
Earth the appliance before making any electrical
connections.
WARNING
If the power cable is damaged, it must be replaced by the
manufacturer, its after sales service or persons with
similar qualifications in order to obviate any danger.
Make the electrical connections of the appliance according to:
4
The instructions of the prevailing standards.
4
The instructions on the circuit diagrams provided with the
appliance.
4
The recommendations in the instructions.
CAUTION
Separate the sensor cables from the 230 V cables.
4
Outside the boiler: Use 2 pipes or cable guides at
least 20 cm apart.
All connections are made with the terminal boxes designed for that
purpose on the back of the boiler's command board. The connection
cables are threaded into the boiler through the space provided
between the top panel and the upper rear panel. These cables will be
fixed on to the control panel with cable clips (supplied in a separate
bag).
Power the appliance via a circuit which includes a remote omnipolar
switch with a gap of more than 3 mm.
The available output per outlet is 450 W (2 A, with cos
j
= 0.7) and
the inrush current must be lower than 16 A. If the load exceeds either
of these values, the control must be relayed using a contactor that
must not be installed in the control panel under any circumstances.
CAUTION
Failure to comply with these instructions could lead to
interference and control unit malfunctioning or even
damage to the electronic circuitry.
4. Installation
AGC 10/15 - AGC 15 - AGC 25 - AGC 35
38
20/01/2012 - 300026081-001-B