26
5.2 ELECTRICAL CONNECTIONS FOR 230V MODELS
Execute the wiring following the directions of “Table 2” and diagrams on page 27.
WARNING
To ensure an appropriate level of electrical safety always keep the 230V power supply cables apart (minimum 4mm in the
open or 1 mm through insulation) from low voltage cables (motors power supply, controls, electric locks, aerial and auxiliary circuits
power supply), and fasten the latter with appropriate clamps near the terminal boards.
WARNING
Connect to the power supply 230 V ~± 10% 50 Hz through a multi pole switch or a different device that can ensure multi pole
disconnection from the power supply, with a contact opening of 3 mm.
WARNING
To connect the encoder to the control panel, use only a dedicated cable 3x0,22mm
2
.
Tabella 2 “collegamento alle morsettiere”
1-2
230 V ~ ±10% (50/60 Hz) power supply input
3-4-5
Operator 1 output 230 V ~ max 600W
6-7-8
Operator 2 output 230 V ~ max 600W (if present)
9-10
230 V ~ max 150 W output for open gate warning light (if P052=0) or courtesy light (if P052>1)
11-12
Flashing light output 230 V ~ max 40W
13-14
13 (-)
“Boost” output for electric-lock, max 1 x art. 110 (if P062=0), 24V pulse output, max 5W (if P062=1), step
by step (if P062=2), electro-brake output for not self-locking operators (if P062=3), output for electric-lock
power supply via external relay (if P062=4), output for electro-magnets power supply for barriers (ifP062=5)
or temporized output (if P062>5).
14 (+)
15-16
Output 24V
max 100mA; by selecting the FL/WL jumper, you can choose the 230 Flash output as a 24V
output (if the jumper is set to FL) or as a Warning light output (if jumper set to WL).
Warning:
the output capacity allows to use LED flashing lights only
17-18
17 - N.C.
Input 6 FCC 1. If it intervenes it stops M1 closing.
If unused, short circuit
.
If
the
installation
req
uires
dif
ferent
comman
-
ds
and
/
or
additi
onal
to
the
standar
d,
you
can
configure each in
put t
o the req
uired rat
e.
R
ef
er t
o Chap
ter
“
Adv
anced Programming”.
18 - Com
19-20
19 - N.C.
Input 5 FCA 1. If it intervenes it stops M1 opening.
If unused, short circuit
.
20 - Com
21-22
21 - N.C.
Input 4 PHOTO 1. When enabled (see parameter P050 in the table), activation of PHOTO
1 provokes: an inversion of direction (during closing), the arrest of the movement (during
opening), prevent the start (gate closed).
If unused, short circuit
.
22 - Com
23-24
23 - N.C.
Input 3 SAFETY. If activated, it causes the inversion. See P055 and P056 on the parame-
ters table.
If unused, short circuit
.
24 - Com
25-26
25 - N.O.
Input 2 PED. If activated, it opens motor nr. 1 only.
26 - Com
27-28
27 - N.O.
Input 1 START. In case of intervention it provokes: the operator opening or closing. It may
operate as “inversion” mode (P049=0) or “step by step” mode (P049=1).
28 - Com
29
Aerial signal input
30
Ground aerial input
31-32
24 V ~ power supply output for auxiliary devices
(AUX + ST)
=
max 200mA
33-34
33 (+)
24 V
power supply output for controlled safety devices
34 (-)