Installazione flussostato
Individuare una posizione idonea per l'installazione del flussostato. Il flussostato dovrebbe essere installato
su una sezione diritta del tubo con un diametro massimo di 5, in entrambe le direzioni, tra il flussostato ed
eventuali pompe, valvole o raccordi. Questo garantirà che la paletta sia esposta a un flusso non turbolento e
che offra una risposta sicura e stabile.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
Il flussostato può essere installato in tubi verticali o orizzontali, sia sul lato che sulla parte posteriore del tubo.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.
Il flussostato non deve essere installato sul lato inferiore di tubi orizzontali.
FLOW SWITCH INSTALLATION – SCMAX
Locate a suitable position to install the flow switch. The flow switch should be installed on a straight section of pipe
with a minimum of 5 pipe diameters, in either direction, between the flow switch and any pumps, valves, or fittings.
This will ensure that the paddle is exposed to non-turbulent flow and giving a steady and stable response.
The flow switch can be installed in vertical or horizontal pipes, either on the side or on the top of the pipe.
The flow switch should not be mounted on the underside of horizontal pipes.
5 x pipe dia.
minimum.
5 x pipe dia.
minimum.