3. Enter the menu item by pressing the
ENTER
button.
4. You see the mnemonic:
on the display.
The digit “1” is blinking indicating that it can be modify.
It’s meaning is: first correction point.
Enter the menu item by pressing the
ENTER
button.
5. You see on the display:
(Factory default).
The left digit (
) is blinking indicating that it can be modify.
6. Pressing the
►
button you can select the next digit.
7. Pressing the
▲
button you can increase the value of the
blinking digit:
,
,
,
,
,
,
,
,
,
,
, etc.
8. When the left digit is selected, pressing
▲
button, the
sequence is:
,
,
,
,
,
,
,
,
,
,
,
, etc.
So you can enter the desired temperature value between
-200.0 °C - 800.0 °C.
9. Type-in the first temperature value taken from the table
above: 70.0 °C:
.
10. After entering the temperature value press
MENU
button, than you can type-in the correction resistance value
(Rn - Rm) in two decimal format.
Factory default value is: 0.00 Ohm:
.
You can modify this value to the value taken from the table
above. The range of the correction resistance value is
between: -2.00 Ohm-2.00 Ohm.
This value is in this example 0.32 Ohm:
.
Содержание DT4120 Series
Страница 1: ...DT4120 xx xx PS Temperature Resistance Potentiometer Meter Transmitter Operating Instructions...
Страница 84: ...DT4120 xx xx PS 84 20170324 V0 10 2 Application example Analog output option...
Страница 85: ...DT4120 xx xx PS 20170324 V0 85 RS232 communication interface option...
Страница 86: ...DT4120 xx xx PS 86 20170324 V0 RS485 communication interface option...
Страница 87: ...DT4120 xx xx PS 20170324 V0 87 RS485 bus topology...
Страница 90: ...DT4120 xx xx PS 90 20170324 V0...
Страница 91: ...DT4120 xx xx PS 20170324 V0 91...
Страница 92: ......