7.4. OVERRIDE 

This function makes it possible to force a muting condition, if it is 
necessary to start the machine despite one or more rays have been 
interrupted by the material. The aim is that of removing from the 
protected area the material which has possibly gathered before the 
photocells for instance because of a failure of the machine cycle. 
Let’s suppose that a pallet has stopped before one or more used 
optical devices; the conveyor belt cannot be started again because 
the control unit - after having detected one or more interrupted rays - 
will not close the output relays, thus making it impossible to free the 
controlled area. 
By starting the override function, it will be possible to carry out this 
operation. 

 

7.5.  STARTING THE OVERRIDE FUNCTION 

• 

Switch off the device. 

• 

Make sure that the test e start buttons are connected. (N.C. for 
the test button, N.O. for the start button). 

• 

Switch on the device. 

• 

Within 10 seconds, press together the test and reset buttons 
and keep pressing. (At each switching on operation, a test is 
carried out to check that the buttons are not locked). 

• 

The override function has been activated. The display 
visualizes three overlapping segments. The muting lamp blinks 
to signal the barrier disconnection. 

• 

The maximum duration of the override function amounts to 60 
seconds after that the barrier is connected again even if the 
buttons are pressed. Obviously, if the buttons are released 
before this time has elapsed, the override function will be 
immediately stopped. 

 

7.6.  TIMING RESTRICTIONS (muting function) 

a) The request of 

muting

 must occur according to the correct time 

sequence: rispectively for the two 

muting

 channels, it is necessary 

to activate input MUTE_A or MUTE_C at first and then input 
MUTE_B or MUTE_D. The request of this last one must arrive 
within a maximum time of 3 seconds. If not the 

muting

 request will 

not be activated. A wrong sequence on the entrances of 

muting

 

shows a mistake on the 

display

 and the relais are open, waiting 

for the pressure of the 

restart 

buttons. 

7.4. 

OVERRIDE 

Questa funzione consente di forzare una condizione di 

muting 

totale, 

qualora occorra avviare la macchina nonostante uno o più raggi 
siano interrotti dal materiale. Lo scopo è quello di liberare l’area 
protetta da eventuale materiale accumulato davanti alle fotocellule a 
seguito ad esempio, di un’anomalia del ciclo macchina. 
Supponendo che un 

pallet

 si sia fermato davanti ad una o più ottiche 

impiegate, il nastro trasportatore non potrà essere riavviato in quanto 
la centralina rilevando uno o più raggi interrotti non chiuderà i relé di 
uscita non consentendo la liberazione dell’area controllata. 
Mediante l’avvio della funzione di 

override

 sarà invece possibile 

effettuare tale operazione. 
 

7.5.  AVVIO DELLA FUNZIONE OVERRIDE 

• 

Spegnere l’apparecchiatura. 

• 

Verificare che i pulsanti di 

test

 e 

start

 siano collegati. (N.C. per 

il 

test

, N.A. per 

start

). 

• 

Accendere l’apparecchiatura. 

• 

Entro 10 secondi premere insieme i pulsanti di 

test

 e 

start

, e 

mantenerli premuti. (Ad ogni accensione viene effettuata una 
verifica per controllare che i pulsanti non siano bloccati) 

• 

La funzione 

override

 è attivata. Il 

display

 visualizza tre 

segmenti sovrapposti. La lampada di 

muting

 lampeggia, per 

segnalare l’esclusione della barriera. 

• 

La durata massima della funzione di 

override

 è di 60 secondi, 

trascorsi i quali, anche se i pulsanti sono premuti viene 
reinserita la barriera. Ovviamente se i pulsanti dovessero 
essere rilasciati prima di questo tempo la funzione 

override

 

cesserà immediatamente. 

 

7.6.  VINCOLI TEMPORALI (funzione di muting) 

a) La richiesta di 

muting

 deve avvenire secondo la sequenza 

temporale corretta: rispettivamente ai due canali di 

muting

 prima 

deve essere attivato l'ingresso MUTE_A o MUTE_C quindi 
l'ingresso MUTE_B o MUTE_D. La richiesta su quest'ultimo deve 
pervenire entro un tempo massimo di 3 secondi. In caso contrario 
la funzione di 

muting

 non verrà attivata. Un sequenza errata sugli 

ingressi di 

muting

 visualizza un errore sul 

display

 ed i relè sono 

aperti, in attesa della pressione del pulsante di 

restart

Содержание BWS-T4N Series

Страница 1: ...1 DATASENSOR BWS T4N SERIES Barriera di sicurezza pluriraggio di livello 4 1 4 coppie di fotocellule Multiray safety barrier level 4 1 4 pairs of photocells MANUALE ISTRUZIONI INSTRUCTIONS MANUAL...

Страница 2: ...ility that the product s BWS T4N AND BWS T4N MT SAFETY CONTROLLER TYPE 4 to which this declaration relates in conformity with the following standard s or other normative document s CEI EN 55022 JUNE 1...

Страница 3: ...SPLAY OPERATIVE CODES 23 12 1 OPERATIVE STATE SIGNALINGS 23 12 2 FAILURE SIGNALINGS 23 13 OVERALL DIMENSIONS 25 INDICE 1 PRIMA DELL UTILIZZO 1 1 1 INDICAZIONI GENERALI 1 1 2 MANUTENZIONE PERIODICA 1 1...

Страница 4: ...ssible chemical agents used during the production processes cannot damage the photocells 1 PRIMA DELL UTILIZZO 1 1 INDICAZIONI GENERALI Per una corretta installazione attenersi scrupolosamente alle is...

Страница 5: ...r the processing of wood glass and ceramic products Automatic warehouses Conveying lines Palletizers 2 GENERALIT E PRINCIPALI APPLICAZIONI La barriera pluriraggio di sicurezza della serie BWS T4N stat...

Страница 6: ...Safety of machinery electro sensitive protective devices Particular requirements for system using active opto electronic devices La progettazione della barriera stata eseguita con riferimento alle seg...

Страница 7: ...e During the operation this feature makes it possible to connect or disconnect any available optical device from the protection function by respecting special times 3 FUNZIONAMENTO L elettronica di co...

Страница 8: ...itch please refer to par 7 1 Even the models showing this feature can be both with manual and automatic restoring Le ottiche che durante il funzionamento dovranno essere poste in muting possono essere...

Страница 9: ...reflections Object TX bar RX bar A A 2 2 2 2 reflective material reflective material 4 PRECAUZIONI E CRITERI DI INSTALLAZIONE L ambiente in cui deve essere installata la barriera deve essere compatib...

Страница 10: ...ll S30 with terminal board connect these terminals with 6 of the photocell 5 COLLEGAMENTI 5 1 RIFERIMENTI SULLA MORSETTIERA Viene riportata una tabella nella quale sono indicati per ciascun numero pre...

Страница 11: ...BILE ESTERNO LAMPADA ESTERNA T E S T N C S T A R T N A GND Contatti dei sensori di muting N A BWS T4N MT control unit Contatto 2 di sicurezza Contatto 1 di sicurezza N C S10 TYPE Emettitore S5 TYPE Ri...

Страница 12: ...terminal board of the control until and on the photocell one In particolare si noti quanto segue Sono state collegate tre fotocellule su quattro tra quelle che possono essere utilizzate il modello S5...

Страница 13: ...tic connection to terminal board S30 5 F50 2PST4 receiver plastic with connector M12 I cavi di collegamento delle fotocellule di richiesta di muting di start e test devono essere schermati con sezione...

Страница 14: ...fying their mutual position for instance by positioning some pairs of emitters on the other receiver side 6 PROCEDURA DI ALLINEAMENTO Dopo avere effettuato il corretto montaggio meccanico ed i corrett...

Страница 15: ...lls the control unit is locked 7 PROCEDURE OPERATIVE 7 1 CONFIGURAZIONE DEI DIP SWITCH La configurazione indicata in tabella deve essere selezionata su entrambi i dip switch presenti sul fianco della...

Страница 16: ...Series Instructions manual Serie BWS T4 Manuale istruzioni 13 13 Almeno una coppia di fotocellule deve essere collegata in caso contrario condizione con tutte le fotocellule escluse la centralina si...

Страница 17: ...the last muting sensor before the new material has reached the first sensors 7 3 FUNZIONE DI MUTING 7 3 1 DESCRIZIONE La funzione di muting consente di escludere o includere una o pi ottiche durante...

Страница 18: ...contact of B2 24 VDC BWS T4 MT terminals 9 MUTE A 8 MUTE B D L v 11 MUTE C 10 MUTE D Nella pagina precedente disegnato un esempio di installazione di una protezione disposta su un trasportatore che d...

Страница 19: ...ing sensors and only photocell S1 Power cable Light cable Muting cable RX cable TX cable Muting signalizer Start Test button Protect the cables BWS T4 control unit Applicazione con due sensori di muti...

Страница 20: ...ding intrusions in unwished moments S3 S4 B4 A4 B3 A3 S1 S2 A2 B1 A1 Manipulator activity B2 N C A1 B1 S A2 B2 d1 Collegamento dei sensori di muting contatto di A1 contatto di A2 contatto di B1 contat...

Страница 21: ...nit must be located in a cabinet with protection degree of at least IP54 Collegamento dei sensori di muting contatto di A1 contatto di A2 contatto di B1 contatto di B2 morsettiera BWS T4N 9 MUTE A 8 M...

Страница 22: ...equence on the entrances of muting shows a mistake on the display and the relais are open waiting for the pressure of the restart buttons 7 4 OVERRIDE Questa funzione consente di forzare una condizion...

Страница 23: ...e closed At paragraph 12 the description of the coding visualized on the display is reported b Da quando lo stato di muting attivo un oggetto pu permanere per un tempo non superiore a 60 s altrimenti...

Страница 24: ...which the barrier is working 8 CONTROLLI FINALI Controllare che l area protetta dalla barriera sia libera da ostacoli verificare il corretto intervento dell apertura dei rel di sicurezza con l interru...

Страница 25: ...ier to DATASENSOR S p A always indicating the detected failure and the operational period 10 INFORMAZIONI GENERALI E DATI UTILI La sicurezza DEVE fare parte della nostra coscienza I dispositivi di sic...

Страница 26: ...0V Muting signalling incandescent lamp 24 V 3 W min 300 mA max screw fastened E10 11 DATI TECNICI Tensione di alimentazione 24 Vdc 10 Assorbimento 420 mA max per tutti i modelli Fotocellule abbinabili...

Страница 27: ...signalling lamp 4 8 System irreversible error or error on the output relays 2 9 Wrong sequence muting request 5 12 CODICI OPERATIVI DISPLAY 12 1 SEGNALAZIONI DI STATO OPERATIVO Codice Descrizione H At...

Страница 28: ...y open this situation does not compromises the safety functioning of the barrier Procedure da attivare nel caso in cui siano visualizzate codifiche di guasto sul display 1 con questo tipo di guasto ve...

Страница 29: ...X1 RX2 TEST TX3 TEST TX4 TX3 TX4 TEST TX1 TEST TX2 GUARD BREAK TX1 TX2 20 17 21 25 29 26 32 30 MUTING SENSOR C A BWS T4N DATASENSOR 13 DIMENSIONI D INGOMBRO Unit di controllo BWS T4N mm 118 73 152 18...

Страница 30: ...D POWER ON LED 3 2 OUTPUT LED STABILITY LED STABILITY LED 24 24 4 0 4 0 L L X1 10 X1 10 8 0 16 6 5 0 16 6 16 0 M18x1 M12 M18x1 mm FOTOCELLULA S5 5 16 6 8 0 22 1 M12 5 0 X1 L 8 0 4 0 M18x1 23 5 LED DI...

Страница 31: ...OCELL S30 5 26 18 5 POWER ON LED OUTPUT LED STABILITY LED mm 32 32 0 20 0 8 4 73 8 5 6 85 46 M5x10 18 6 11 0 18 OUTPUT LED 27 M12x1 FOTOCELLULA S30 5 26 18 5 LED POWER ON LED DI USCITA LED STABILITY m...