4. Installation
4.1.
Rack Mounting
The iBoot-PDU
is designed for mounting in a standard 19” equipment cabinet.
There are two L-shape brackets marked as
“L” and “R”, install the “L” bracket on the left side of the iBoot-
PDU chassis then the
“R” bracket on its right side.
Installed L bracket:
Installed R bracket:
Install the iBoot-PDU to the standard 19-inch rack.
4.2.
Ethernet
The iBoot-PDU has a 10/100 Ethernet port. The default address is 192.168.0.254 or as set by a DHCP Server
on initial power up.
4.3.
Power Source
The
iBoot-PDU4-N15 and iBoot-PDU8-N15
provide a linecord for connection to a 15 Amp
115VAC service. The total maximum current load
for all outlets on the these models cannot exceed
12 Amps.
The
iBoot-PDU8-2N15 provides
two linecords for
connection to 15 Amp 115VAC services. The total
maximum current load for outlets on any linecord
cannot exceed 12 Amps. Each linecord distributes
power to four outlets.
The
iBoot-PDU4-N20 and iBoot-PDU8-N20
provide a linecord for connection to a 20 Amp
115VAC service. The total maximum current load
for all outlets on the these models cannot exceed
16 Amps.