iBoot-PDU_v170515e
iBoot-PDU User Manual
Page 10
The
iBoot
‐
PDU8
‐
2N20
provides two linecords for
connection to 20 Amp 115VAC services. The total
maximum current load for outlets on any linecord
cannot exceed 16 Amps. Each linecord distributes
power to four outlets.
The
iBoot-PDU4-C10 and iBoot-PDU8-C10
are
for international applications and can be used on
100V to 240VAC. These models provide an IEC
320 style universal inlet for connecting a
detachable power cord. A standard IEC to CEE7
European cord set is supplied with the unit for use
on 10 Amp 240VAC service*. The total maximum
current load for all outlets cannot exceed 12 Amps
at 115VAC or 10 Amps when used at 240VAC.
The
iBoot-PDU8-2C10
is for international
applications and can be used on 100V to 240VAC.
The iBoot-PDU8-2C10
provides two IEC 320 style
universal inlets for connecting a detachable power
cord. Two standard IEC to CEE7 European cord
sets are supplied with the unit for use on 10 Amp
240VAC service*. The total maximum current load
for outlets on any linecord cannot exceed 12 Amps
at 115VAC or 10 Amps when used at 240VAC.
Each linecord distributes power to four outlets.
The
iBoot-PDU4-C20 and iBoot-PDU8-C20
is for
international applications and can be used on 100V
to 240VAC. The iBB-C20 provides an IEC 320 style
universal inlet for connecting a detachable power
cord. A standard IEC to CEE7 European cord set is
supplied with the unit for use on 20 Amp 240VAC
service*. The total maximum current load for all
outlets cannot exceed 16 Amps.
The
iBoot-PDU8-2C20
is for international
applications and can be used on 100V to 240VAC.
The iBoot-PDU8-2C20
provides two IEC 320 style
universal inlets for connecting a detachable power
cord. Two standard IEC to CEE7 European cord
sets are supplied with the unit for use on 16 Amp
240VAC service*. The total maximum current load
for outlets on any linecord cannot exceed 16 Amps.
Each linecord distributes power to four outlets.
* Power cords for other countries are available from your local source. If a power cord with a different
terminating plug is required, be sure it is properly rated and meets all the required local electrical standards.