Installation - 2.15
Figure 2.16 - RS232 control signals
The RTS232 and CTS232 signals control data transmission and synchronize
the connected devices.
If the RTS/CTS handshaking protocol is enabled, the DS41 activates the
RTS232 output to indicate a message is to be transmitted. The receiving unit
activates the CTS232 input to enable the transmission.
RS485 non polled interface
The RS485 NON POLLED interface is a Full Duplex interface.
The NON POLLED configuration is used for point to point connections over
longer distances than those acceptable for RS232 communications or in
electrically noisy environments.
The following pins of the 25-pin connector are used for RS485 NON
POLLED communications:
Pin
Name
Function
2
TX485+
RS485 output (+)
4
TX485-
RS485 output (-)
3
RX485+
RS485 input (+)
5
RX485-
RS485 input (-)
7
SGND
Signal Ground