DPR-350 User Manual Ver_01 Firmware V-1.0
K91D01-EN - 51 -
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
THD-I Alarm Latching
-
0
1
1
0: non-latching
1: latching
Voltage Unbalance Alarm
%
0
50
0
If voltage unbalance exceeds his value,
an alarm occurs.
If this value is set to 0, the alarm is not
checked.
Voltage unbalance is calculated as the
maximum deviation from the average.
Voltage Unbalance Alarm
Timer
Sec
0
255
30
If voltage unbalance is above the limit
for this duration, an alarm occurs.
Voltage Unbalance Alarm
Latching
-
0
1
1
0: non-latching
1: latching
Current Unbalance Alarm
%
0
50
0
If current unbalance exceeds his value,
an alarm occurs.
If this value is set to 0, the alarm is not
checked.
Current unbalance is calculated as the
maximum deviation from the average.
Current Unbalance Alarm
Timer
Sec
0
255
30
If current unbalance is above the limit
for this duration, an alarm occurs.
Current Unbalance Alarm
Latching
-
0
1
1
0: non-latching
1: latching
kW tick type
-
0
2
1
0: Always
1: If Group 1 counters are active
2: If Group 2 counters are active
Connection Type
(Topology)
-
0
0: 3 phase, 4 wire, star
1: 1 phase, 2 wire
2: 2 phase, 3 wire
3: 3 phase, 3 wire, delta
4: delta high-leg
5: 3 phase, 3 wire, L1-L2 CT
6: 3 phase, 3 wire, L1-L3 CT
Demand Time Interval
min
1
240
15
The recalculation period for demand
values.
Energy Counter Unit
-
0
1
0
0: kWh
1: MWh
20.2. ELECTRICAL PARAMETERS GROUP
Содержание DPR-350 Series
Страница 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...
Страница 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...
Страница 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...