DPR-350 User Manual Ver_01 Firmware V-1.0
K91D01-EN - 48 -
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
Language Selection
-
0
1
0
0:
English
1:
Turkish. This option can vary
according to the country of use.
Different languages can be uploaded
using Rainbow Plus software.
Intermittent Relay Timer
Sec
0
255
1
If Intermittent Relay Active parameter is
set to 1, the horn relay engages and
disengages intermittently for the
duration of this timer.
Horn Timer
Sec
0
120
60
If a warning or an alarm occurs, the
HORN
output is energized for the
duration of this timer. If this timer is set
to 0, the horn output is energized
indefinitely.
Periodic Record Timer
Min
0
65000
60
Sets the periodic event record timer
RS-485 Enable
-
0
1
1
0:
RS-485 port disabled
1:
RS-485 port enabled
Modbus Address
-
0
254
1
This parameter is the Modbus address
of the device.
RS-485 Communication
Rate
Baud
2400 115200
9600
RS-485 Modbus port communication
rate
Intermittent Relay Active
-
0
1
0
0:
continuous
1:
intermittent
Alarm Event Record
-
0
1
1
0: Disabled 1: Enabled
Warning Event Record
-
0
1
1
0: Disabled 1: Enabled
Digital Input 1 Event
Record
-
0
1
1
0: Disabled 1: Enabled
Digital Input 2 Event
Record
-
0
1
1
0: Disabled 1: Enabled
Digital Input 3 Event
Record
-
0
1
1
0: Disabled 1: Enabled
Digital Input 4 Event
Record
-
0
1
1
0: Disabled 1: Enabled
Programming Event
Record
-
0
1
1
0: Disabled 1: Enabled
Reset Event Record
-
0
1
0
0: Disabled 1: Enabled
Output Event Record
-
0
1
1
0: Disabled 1: Enabled
Periodic Event Record
-
0
1
0
0: Disabled 1: Enabled
LCD Backlight Timer
Min
0
1440
0
If no buttons are pressed in this
duration, the LCD backlight turns off.
Flashing Relay ACTIVE
Timer
Min
0
6000
0
Flashing relay ACTIVE timer.
Flashing Relay PASSIVE
Timer
Min
0
6000
0
Flashing relay PASSIVE timer.
Internal Record Period
Sec
2
65000
60
Configures the frequency of records in
the internal memory. More frequent
records will cause the memory to fill
quickly. Once memory is full, the oldest
record will be deleted.
Modbus Packet Type
0
1
0
Do not change this parameter. Affects
the Modbus map structure.
20. PROGRAM PARAMETER LIST
20.1. CONTROLLER CONFIGURATION GROUP
Содержание DPR-350 Series
Страница 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...
Страница 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...
Страница 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...