DPR-350 User Manual Ver_01 Firmware V-1.0
K91D01-EN - 52 -
The unit features 4 digital inputs. The parameters of one digital input are explained below. The other input
functions have identical parameters.
Input functions can be assigned user defined strings. This enables digital inputs to be used in any
function.
Each digital input has the following programmable parameters:
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
Latching
-
0
1
0:
non-latching. The alarm pop-up
screen is dismissed once the fault
condition is removed.
1:
latching. The alarm pop-up screen
remains until manually dismissed even
if the fault condition is removed.
Delay Timer
-
0.1
10
The duration between receiving a fault
signal and raising the alarm.
Contact Type
-
0
1
0:
Normally open
1:
Normally closed
Input Function
-
0
99
Selected from list of pre-defined input
functions. Any function from the list
below can be selected. If a user
function is selected, the display name
will be a user input string.
0:
User Function-1
10:
Alarm Mute
11:
High Temperature
12:
Panel Lock
DIGITAL INPUT FUNCTION LIST
No
Description
0
User Function 1
1
User Function 2
2
User Function 3
3
User Function 4
4
User Function 5
5
Input Counter 1 Reset
6
Input Counter 1 Increment
7
Input Counter 2 Reset
8
Input Counter 2 Increment
9
Change Counter Group
10
Alarm Mute
11
High Temperature
12
Panel Lock
13
Breaker Closed Contact
14
Breaker Open Contact
20.3. INPUT PARAMETERS
Input functions can only be assigned custom names
using Rainbow Plus program.
Содержание DPR-350 Series
Страница 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...
Страница 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...
Страница 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...