DPR-350 User Manual Ver_01 Firmware V-1.0
K91D01-EN - 60 -
This feature is used to prevent unnecessary trips which may occur in cases where the load is powered up
suddenly after remaining unpowered for a long period of time. Only valid for
“OVERCURRENT
PROTEC
TION (ANSI 50/51)”
. The protections are valid for the parameter group defined in this section
for a set duration after the system has been energized.
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
TCOLDTD
Sec
0
14400
7200
If the load is not energized for this
period, it is designated as cold load.
TCLPTD
Sec
0
14400
7200
The cold load condition is removed
after this period is elapsed upon
energizing.
I>1 Status
-
0
1
0
Active for level 1 protection
I>1 Current Setting
In
0.08
4.00
1.50
Current threshold for level 1 protection
I>1 Delay Timer
Sec
0.00
100.00
1.00
Constant time delay for level 1
protection.
I>1 TMS
-
0.025
1.200
1.000
Time multiplier for level 1 protection
IEC curves
I>1 Time Dial
Sec
0.5
15.0
7.0
Time multiplier for level 1 protection
IEEE curves
I>2 Status
-
0
1
0
Active for level 2 protection
I>2 Current Setting
In
0.08
40.00
1.50
Current threshold for level 2 protection
I>2 Delay Timer
Sec
0.00
100.00
1.00
Constant time delay for level 2
protection
Function Configuration Screen
When a password is entered for programming or manual control, it is valid for 2 minutes. Entering
programming or manual control does not require a password within this period. This feature can be
enabled to make the system ask for the password, ignoring the 2 minute password period.
20.19. COLD LOAD PICKUP
20.20. SAFE EXIT
Содержание DPR-350 Series
Страница 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...
Страница 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...
Страница 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...