The DPR-350 controller offers constant time and 12 different variable time curves for protection functions.
Current / time curves are usually calculated using the equation below:
Here :
t(I) = Trip time as a function of input current I
I = Instantaneous secondary current value of the phase
Is = Fault threshold for secondary current
T = Time coefficient (TD for IEEE, TMS for IEC)
β = Constant for the given curve
α = Constant for the given curve
L = Constant for IEEE, 0 for IEC
C = Constant additional delay
CURVE
STANDARD
β
α
L
Constant Time
DT
Standard Inverse
IEC
0.14
0.02
0
Very Inverse
IEC
13.5
1
0
Extremely Inverse
IEC
80
2
0
Long Time Inverse
UK
120
1
0
RI (electromechanical)
RI
,K between 0.1-10
Moderately Inverse
IEEE
0.0515
0.02
0.114
Very Inverse
IEEE
19.61
2
0.491
Extremely Inverse
IEEE
28.2
2
0.1217
Inverse
US
5.95
2
0.18
Short Time Inverse
US
0.16758
0.02
0.11858
IDG
IDG
Rectifier
UK
45900
5.6
0
10.2. TIME CALCULATION FOR CURVES