DPR-350 User Manual Ver_01 Firmware V-1.0
EFFECT OF PHASE SWAPPING
The utility mains is still loaded with 100 kW on each phase. PF in phases L2 and L3 will show -0.50 due
to phase shift between voltages and currents which is caused by CT swapping. As a result, the total
power displayed will be 0 kW.
Measured values are as follows:
kW
kVAr
kVA
pf
Phase L1
100.0
0.0
100
1.00
Phase L2
-50.0
86.6
100
-0.50
Phase L3
-50.0
-86.6
100
-0.50
Total
0.0
0.0
300
0.0
Number of Inputs:
4 inputs, all configurable.
Input Type:
Optically isolated, digital input
Function Selection:
From list
Contact Type:
Normally open or normally closed (programmable)
Minimum Sensing
Duration:
250ms
Active Signal Level:
40-135V-DC or 30-265V-AC
Isolation:
1000VAC, 1 minute
Noise Filtering:
Var
Structure:
Relay output, normally open contact, single common terminal free
contact output.
Max. Switching Current:
5A @250VAC
Max. Switching Voltage:
250VAC
Max. Switching Power:
1250VA
3.4. DIGITAL INPUTS
3.5. RELAY OUTPUTS