DPR-350 User Manual Ver_01 Firmware V-1.0
K91D01-EN - 49 -
Parameter Definition
Unit
Min
Max
Factory
Setting
Description
Current Transformer
Ratio
-
5/5
25000/1
600/1
Enter the primary and secondary values
for the current transformer.
Voltage Transformer
Ratio
-
0
5000
1.0
Voltage transformer ratio. This ratio is
multiplied by the values measured in
the voltage and power measurements.
If no transformers are used, this value
must be set to 1.0.
Alarm End Timer
Sec
0
255
20
When the alarm cause is removed, the
alarm ends after this duration unless it
is latching type.
Phase Order Check
-
0
1
0
0: phase order not checked
1: alarm occurs if phase order is faulty.
Low Voltage Alarm
V
0
65000
0
If one of the phase voltages drops
below this value, the unit concludes that
mains power is lost.
If this value is set to 0, it is not checked.
High Voltage Alarm
V
0
65000
0
If one of the phase voltages exceeds
this value, the unit concludes that mains
power is faulty.
If this value is set to 0, it is not checked.
Voltage Fault Delay
Sec
0
255
30
If phase voltages are outside the limits
for this duration, the unit concludes that
mains power is faulty.
Voltage Alarm Latching
-
0
1
1
0: non-latching
1: latching
Low Frequency Alarm
Hz
0
400
0
If the mains frequency drops below this
value, an alarm occurs.
If this value is set to 0, the alarm is not
checked.
High Frequency Alarm
Hz
0
400
0
If mains frequency exceeds this limit, an
alarm occurs.
If this value is set to 0, the alarm is not
checked.
Frequency Alarm Timer
Sec
0
255
30
If mains frequency is outside the limits
for this duration, an alarm occurs.
Frequency Alarm
Latching
-
0
1
1
0: non-latching
1: latching
Low Active Power Alarm
kW
0
9999
0
If the active power of any channel drops
below this value, an alarm occurs.
If this value is set to 0, the alarm is not
checked.
High Active Power Alarm
kW
0
9999
0
If the active power of any channel
exceeds this value, an alarm occurs.
If this value is set to 0, the alarm is not
checked.
Active Power Alarm
Timer
Sec
0
255
30
If the active power of any channel is
outside the limits for this duration, an
alarm occurs.
Active Power Alarm
Latching
-
0
1
1
0: non-latching
1: latching
20.2. ELECTRICAL PARAMETERS GROUP
Содержание DPR-350 Series
Страница 20: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 2 3 PHASE 4 WIRE STAR 4 3 3 PHASE 3 WIRE DELTA...
Страница 21: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 4 3 PHASE 4 WIRE DELTA 4 5 3 PHASE 3 WIRE DELTA 2 CT L1 L2...
Страница 23: ...DPR 350 User Manual Ver_01 Firmware V 1 0 4 8 1 PHASE 2 WIRE...
Страница 24: ...DPR 350 User Manual Ver_01 Firmware V 1 0 5 CONNECTION DIAGRAM...