DKG-507 User Manual V-42
(24.05.2013)
- 38 -
PGM
Parameter Definition
Unit
Fact.Set Description
P_075
Single phase Enable
-
0
0:
3-phase system
1:
Single phase system
P_076
Emergency Backup
Operation
-
0
0:
In TEST mode, the load will not be transferred
to the genset even if the mains fail.
1:
In TEST mode, the load will be transferred to
the genset if the mains fail.
P_077
Modem Enable
-
0
0:
No modem connection, the serial port is
connected to PC
1:
Modem connected.
P_078
SMS Enable
-
0
0:
SMS not enabled
1:
SMS enabled
P_079
MODBUS Address
-
0
0:
RAINBOW communication protocol.
1-144:
MODBUS communication. This parameter
is also the MODBUS controller address of the unit.
P_080
SMS on Mains
Change
-
0
This parameter controls SMS sending when mains
voltages status is changed. No warning is
generated.
0:
no SMS when mains failed or restored
1:
SMS sent when mains failed or restored
P_081
Fuel Consumption per
Hour
%
0
This parameter is the threshold for sending FUEL
THEFT and FUELLING sms messages.
If this parameter is set to 0, then no Fuel Theft and
Fuelling sms messages will be sent.
If SMS is required, set this parameter to a value
above the hourly fuel consumption of the genset.
P_082
Real Time Clock
Adjust
-
117
This parameter trims precisely the real time clock
circuit.
Values from 0 to 63 speed up the clock with
0.25sec/day steps.
Values from 127 to 64 slow down the clock with
0.25sec/day steps.
P_083
Remote Start Enable
-
0
0:
no Remote Start signal
1:
SPARE-2 input is Remote Start signal
P_084
Simulate Mains
Enable
-
0
0:
no Simulate Mains signal
1:
SPARE-2 input is Simulate Mains signal
P_085
Delayed Simulate
Mains
-
0
0:
The
SPARE-2
input has normal function
1:
The
SPARE-2
input has delayed simulate
mains function. See chapter 6.8 for more info.
P_086
Flashing Relay Timer
hours
0
Delayed Simulate Mains Operation:
max
genset running time after Simulate Mains signal
disappears.
Dual Genset Systems:
flashing relay toggle
timer. Please contact DATAKOM for dual genset
mutual stanby operation.