- 36 -
PGM
Parameter Definition
Unit
Fact.Set Description
P_043
Genset Contactor
Timer
sec
1
This is the period after the mains contactor has
been deactivated and before the generator
contactor has been activated.
P_044
Mains Contactor
Timer
sec
1
This is the period after the generator contactor has
been deactivated and before the mains contactor
has been activated.
P_045
Stop Solenoid Timer
sec
10
This is the maximum time duration for the engine
to stop. During this period the STOP relay output
is energized (if assigned by
Relay Definitions
). If
the genset has not stopped after this period, a
FAIL TO STOP
warning occurs.
P_046
Number of Starts
-
3
This is the maximum number of start attempts.
P_047
Mains Phase Order
Enable
-
0
0:
mains phase order checking disabled
1:
if mains phase order is faulty, then a warning is
given and mains contactor deenergized.
P_048
Genset Phase Order
Loaddump
-
0
0:
genset phase order checking disabled
1:
if genset phase order is faulty, then a loaddump
is generated and the genset stops after cooldown.
P_049
RPM from genset
frequency
-
1
This parameter is used in the conversion of the
genset frequency to engine rpm.
0: read rpm from the optional MPU input
1: convert frequency to rpm (using crank teeth
count)
P_050
Crank Teeth Count
-
30
This is the number of pulses generated by the
magnetic pickup sensing unit in one turn of the
flywheel.
This parameter is also used in the conversion of
the genset frequency to engine rpm. The
frequency in Hz is multiplied with this parameter
during conversion to rpm.
P_051
Low rpm Shutdown
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
alarm is generated and the engine
stops.
P_052
Low rpm Warning
rpm
0
If the engine speed goes under this limit, a
GENSET
LOW SPEED
warning is generated.
P_053
High rpm Warning
rpm
0
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
warning is generated.
P_054
High rpm Shutdown
rpm
0
If the engine speed goes over this limit, a
GENSET
HIGH SPEED
alarm is generated and the engine
stops.
P_055
Alarm Relay Timer
sec
60
This is the period during which the
ALARM
relay
is active. If the period is set to 0, this will mean
that the period is unlimited.
P_056
Intermittent Alarm
Relay
-
0
0:
continuous
1:
intermittent (turns on and off every second)
P_057
Service Engine Hours
hour
50
The
SERVICE REQUEST
led indicator will turn on
after this quantity of engine hours from the last
service. If the period is set to ‘0’ no
SERVICE
REQUEST
will be generated depending on engine
hours.
P_058
Service Period
month
6
The
SERVICE REQUEST
led indicator will turn on
after this amount of time from the last service. If
the period is set to ‘0’ no
SERVICE REQUEST
will
be indicated depending on time.