D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 75 -
Parameter Definition
Unit
Min
Max
Factory
Set
Description
CT Location
-
Gen
Load
Gen
0:
CTs are at the genset side. Mains
currents are not measured.
1:
CTs are at load side. Both mains and
genset currents are monitored following
contactor status.
Reverse CT Direction
-
0
1
0
This parameter is useful to invert all CT
polarities at the same time.
0:
normal CT polarity assumed.
1:
reverse CT polarity assumed.
Unit Functionality
-
0
3
AMF
0: AMF functionality. The unit controls
both engine and load transfer. The
genset starts based on mains status.
1: ATS functionality. The unit controls
the load transfer and issues genset start
signal based on mains status.
2: REMOTE START functionality. The
unit controls engine and alternator. The
genset starts with external signal.
3: RESERVED. Not used.
Data Logging Period
sec
2
3600
2
This parameter adjusts the data logging
frequency to micro-SD or USB Flash
memories. Frequent recording will
require more memory capacity.
With a period of 2 seconds, 4GB per
year of memory is necessary.
With a period of 1 minute, 133MB is
consumed per year.
LCD Backlight Dimming
Delay
min
0
1440
60
If no button is pressed during this
period, then the unit will reduce the LCD
screen backlight intensity in for
economy.
Fuel Filling Timer
sec
0
36000
0
After activation of the fuel pump
function, if the Fuel Pump High Limit
level is not reached, then the fuel pump
will stop for safety.
If this parameter is set to zero, then the
timer is unlimited.
SMS Commands
Enabled
-
0
1
0
0: SMS commands not accepted
1: SMS commands are accepted but
from listed telephone numbers only.
Open with Last Mode
-
0
1
0
0: The unit powers up in STOP mode
1: The unit powers up in the same
operating mode before power down.
Pre-Transfer Delay
sec
0
60
0
If this parameter is not zero, the unit will
activate the Wait Before Transfer output
function during this timer, before
initiating a load transfer.
This function is designed for elevator
systems, in order to bring the cabin to a
floor and open doors before transfer.
E-mail on mains change
-
0
1
0
0: No e-mail at mains status changes
1: E-mails sent at mains status change
Enable Auto not Ready
Warning
-
0
1
0
0: Auto not Ready Warning disabled
1: Auto not Ready Warning enabled
16.1. CONTROLLER CONFIGURATION GROUP (continued)
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...