L058D01-EN - 25 -
Structure:
CANBUS, non isolated.
Connection:
3 wires (CANH-CANL-GND).
Data rate:
250 kbps
Termination:
Internal 120 ohms provided
Common mode voltage:
-0.5 VDC to +15 VDC, internally clamped by transient suppressors.
Max distance:
200m with 120 ohm balanced cable
Description:
USB 2.0, not isolated, HID mode
Data rate:
Full Speed 1.5/12 Mbits/s, auto detecting
Connector:
USB-B (printer connector)
Cable length:
Max 6m
Functionality:
Modbus, FAT32 for firmware upgrade (boot loader mode only)
The USB-Device port is designed to connect the module to a PC. Using the RainbowPlus software,
programming, control of the genset and monitoring of measured parameters are achieved.
The RainbowPlus software can be downloaded from
www.datakom.com.tr
website.
The connector on the module is of USB-B type. Thus A to B type USB cable should be used. This is the
same cable used for USB printers.
The battery voltage must be connected.
3.14. USB DEVICE PORT
3.13. J1939-CANBUS PORT (OPTIONAL)
USB A to B
Cable
USB Device
Connector
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...