D-200 MK2 User Manual Firmware V-6.3
L058D01-EN - 21 -
Type of inputs:
all configurable
Function selection:
from list
Contact type:
Normally open or normally closed (programmable)
Switching:
Battery negative or battery positive (programmable)
Structure:
47 k-ohms resistor to battery positive, 110k-ohms to battery negative.
Measurement:
Analog voltage measurement.
Open circuit voltage:
70% of battery voltage
Low level threshold:
35% of battery voltage
High level threshold:
85% of battery voltage
Maximum input voltage:
+100VDC with respect to battery negative
Minimum input voltage:
-70VDC with respect to battery negative
Noise filtering:
yes
Type of inputs:
all configurable, additional sender ground input
Function selection:
from list
Structure:
667 ohms resistor polarizing to +3.3VDC
Measurement:
Analog resistor measurement.
Open circuit voltage:
+3.3VDC
Short circuit current:
5mA
Measurement range:
0 to 5000 ohms.
Open circuit threshold:
5000 ohms.
Resolution:
1 ohms @ 300 ohms or lower
Accuracy:
2 %+1 ohm (±7 ohms @300 ohms)
Common mode voltage
range:
± 3VDC
Noise filtering:
yes
3.5. ANALOG SENDER INPUTS AND SENDER GROUND
3.4. DIGITAL INPUTS
Содержание D-200 MK2
Страница 30: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 30 4 3 3 PHASE 3 WIRE DELTA 4 2 3 PHASE 4 WIRE STAR ...
Страница 33: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 33 4 9 1 PHASE 2 WIRE 4 8 2 PHASE 3 WIRE DELTA 2 CTs L1 L3 ...
Страница 38: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 38 6 2 AMF FUNCTIONALITY CTs AT ALTERNATOR SIDE ...
Страница 39: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 39 6 3 ATS FUNCTIONALITY ...
Страница 40: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 40 6 4 REMOTE START FUNCTIONALITY ...
Страница 41: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 41 6 5 ENGINE CONTROL FUNCTIONALITY ...
Страница 42: ...D 200 MK2 User Manual Firmware V 6 3 L058D01 EN 42 Feature not applicable to this product 6 6 ...